No longer available - Not for new projects - see one of the newer meters
instead

Model PD690
4 1/2 Digit Universal Process Meter
Model PD690 is a high performance, easy to use,
industrial-grade
microprocessor digital process meter. It accepts all the standard
process
signals: 4-20 mA, 1-5 V, 0-5 V and 0-10 V and displays these signals in
engineering units on a 4 1/2 digit display. The display includes an
extra zero
which may be used to handle numbers up to 199,990.
- Easy Single Button Scaling with Lockout Feature
- 4-20 mA, 0-5 V, or 0-10 V Field Selectable Inputs
- 24
V Transmitter Power Supply Standard
- Stand Alone
Scaling
- Steady, Accurate Display to +/- 199,990
- 11 point Linearization
- Square Root
Extraction
- 4 1/2 Digit + Extra Zero
- NEMA
4X Front Panel
- 2 or 4 Relay = 4-20 mA Output
Options
Stand alone scaling allows the PD690 to
be scaled without applying an input.
Simply select internal calibration (I-CAL) mode and set desired display
for the
4mA and 20 mA value. To scale inputs such as 0 -5 V, 1-5V or 0-10V
without
applying a signal, first complete an initial calibration.
4 Visual Alarms Standard
- Front panel alarm status indication
- Perfect
for 'Visual indication only' applications
- any
combination of high or low set points
- 0-100%
dead-band adjustment
Big bright steady display for big
numbers
- 4 1/2 digit + extra zero display
- Displays
up to +/- 199,990
- 0.56" high efficiency red LED's
- Steady and quick responding display
Powers the loop
The 24 Volt transmitter power supply is standard on the PD690.
This feature
saves time and money by simplifying wiring and eliminating the cost of
an
external transmitter power supply.
NEMA 4X Front Panel
Wet, dirty and dusty environments don't bother the PD690's
NEMA 4X front
panel so it can be installed in almost any panel in the plant
Linearization
- The linearization feature has two modes of
operation:
- The 11 point user calibration
displays non-linear signals
- The square root
extraction displays the flow rate from a differential transmitter.
- 11 point user calibration
- input up to 11 calibration points
- perfect
for non-linear signals
Square Root Extraction
- Displays flow rates
- user
selectable low flow cutoff
- Only two calibration
points required
- accurate to +/- 0.1% FS +/- 1
count from 10-100% of flow
- The square root
extraction feature displays flow rate by extracting the square root of
a signal from a differential pressure transmitter. The user selectable
low flow cut off feature gives a reading of zero when the flow rate
drops below a user-set point.
NEW 18-36 Vdc
POWERED
The PD690 Universal Process Meter can now be powered from
18-86 Vdc. This new
option provides up to 500 Vdc of isolation. All the features and
options
available on the AC powered meters are available on the DC powered
meters.
Note: 18-86 VDC powered PD690's are not UL listed.
Remember
Every PD690 comes with 4 visual alarms standard! The PD690
universal process
meter can be equipped with 2 or 4 relay contacts and a isolated 4-20 mA
transmitter output. These options may be combined in any configuration
to
satisfy a wide variety of applications. A fully loaded model PD690-3
includes 4
relays and a isolated 4-20 mA transmitter output.
Two or four Relays
- 2 or 4 SPDT, 2A @240Vac resistive
- Automatic
or automatic + manual reset
- Fail-safe action and
auto initialization
- 0-100% dead-band adjustment
Isolated 4-20 mA output
- 4-20mA or 20-4 mA output
- 500
Vdc isolation
- With or without relay contacts
Specifications-Basic Meter
- Inputs
:
Field Selectable,4-20 mA, 1-5 V, 0-5 V, 0-10 V.
- Display
:
Bright, Large, 0.56" (14.2mm) high efficiency red LED. 4 1/2 digits +
extra zero; +/- 1999(0),(0) may be switched on to display 199,990.
- Front Panel
: NEMA 4X, panel gasket
provided.
- Calibration
:
Maybe calibrated using internal calibration (I-CAL) or by applying an
external calibration signal (E-CAL).
- Calibration
Range
: 4 mA (1V) input may be set to display
anywhere in range of meter. 20 mA (5V) may be set anywhere above or
below 4MA (5V) may be set anywhere above or below 4 mA input.
- Lockout
: Jumper 3 at rear of instrument
restricts modification of calibration values.
- Loop
Power
: Isolated 24 VDC at 20mA regulated. Noise
less than 10 mV p-p. Max loop resistance of 1200 ohms. Available for
either signal input or 4020 mA output option, but not both.
- Hold
Reading
: Connect terminals HLD and COM.
- Accuracy
: 0.05% of calibrated span.
- Input Impedance
: Voltage ranges,
greater than 100 Kohms: Current range,100 ohms.
- Power
: 115 VAC or 230 VAC +/- 10%, 50/60 Hz, 10 VA.
- Environmental
: Operating temperature range: 0 to 65 deg C.
Storage Temperature range : -40 to 85 deg C. Relative Humidity : 0 to
90% non-condensing.
- Enclosure
:
1/8 DIN, high impact plastic, UL 94V-0.
- Connections
: Removable screw material block (provided).
- Alarm
Points
: 4,any combination of high or low alarms.
- Alarm Status Indication
;
Front Panel LED
- Alarm Dead-band
:
0-100%, User Selectable.
- UL File Number
:
E160849; 508 Industrial Control Equipment.


Relays
- Rating
: 2 or 4
relays; 2 Amp SPDT (form C). The contacts are rated 2 Amp @ 30 VDC or 2
Amp @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC for NC contacts and
1/10 HP @ 125/250 VAC for NO contacts, inductive load.
- Reset
: User Select.
- 1. Automatically when the input passes
the reset point.
- 2. Automatically + manually (via
user supplied switch or front panel ACK button).
- Fail-safe Operation
:
The relay coils are energized in the non-alarm condition. In the case
of a power failure , the relays will go to the alarm state. May be
disabled with internal jumper.
- Auto
Initialization
: When power is applied to the
meter, the relays will always reflect the state of the input to the
meter.
- Dead band
: 0-100 %,
User Selectable.
Isolated 4-20 mA Transmitter Output:
- Calibration Range
:
Anywhere in range of meter, 501 count minimum span.
- Output
Loop Resistance
: 1500 ohms max. using a 35V
external power supply. 500 ohms max. using the built-in loop power
supply. Built-in loop power supply available for either 4-20 mA output
or signal input, but not both.
- Accuracy
: +/- 0.1% FS, +/- .004 mA
- Isolation
:
500 VDC or peak AC, input-to-output or input/output-to-power line.
- External Loop Power Supply
: 35 V max.
Hot tip - Green Lee (800 435 0786) has a 1/8th
DIN panel punch
part # 60068 for the NEMA 4X bezels.
| Order number |
Description |
Repacement |
| PD690-3-N |
No options |
PD6000-6R0
|
| PD690-3-14 |
2
Relays |
PD6000-6R2
|
| PD690-3-15 |
4-20mA
Output |
PD6000-6R3
|
| PD690-3-16 |
2 Relays +
4-20 mA output |
PD6000-6R5
|
| PD690-3-17 |
4
Relays |
PD6000-6R4
|
| PD690-3-18 |
4 Relays +
4-20 mA output |
PD6000-6R7
|
| A -4 may be substituted for the -3 to call
out meters powered from 230Vac at no extra charge. |
|
Prices subject to change.
"> >