FM Approved & CSA Certified as intrinsically safe with entity for use in Class I, Div 1, Groups ABCD; Class II, Div 1, Groups EFG; Class III, Div 1; Class I, Zone 0, Group IIC; T-code = T4. Nonincendive: Suitable for use in Class I, Div 2, Groups ABCD; Class II, Div 2, Groups FG; Class III, Div 2.
Entity Parameters: Ui: 30 V; Ii: 175 mA; Ci: 0; Li: 0; Pi: 1.0 W
| Specifications | |
|---|---|
| Display | 5
digit LCD (-99999 to 99999),15.2mm [0.60"] high, 7-segment, automatic
lead zero blanking. |
| Decimal Point | Up to 4 places (d.dddd, dd.ddd, ddd.dd, dddd.d, or ddddd) |
| Engineering Units display | 6.4mm [0.25"] high, 14-segment. |
| Bar-graph | 20-segment, 0% to 100% indication. |
| Trend arrows | Up and down trend indication. |
| Back-light | Bright orange (intensity varies with signal) |
| Front Panel | FM Type 4X, IP65; panel gasket provided |
| Display Update Rate | 2.5/second |
| Over-range | Display flashes 99999 |
| Under-range | Display flashes -99999 |
| Programming Method | Four front panel buttons |
| Noise Filter | Programmable from 1 to 199 |
| Max/Min Display | Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off. |
| Password | Programmable password restricts modification of programmed settings. |
| Non-Volatile Memory | All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost. |
| Voltage Drop | 2.0 V max w/o back-light, 5.7 V max with back-light |
| Equivalent Resistance | 125 Ω @ 20 mA without back-light, 315 Ω @ 20 mA with back-light. |
| Common Mode Rejection | 64 dB at 50/60 Hz |
| Warranty | 3 years parts and labor (extended warranty available) |
| Environmental and Mechanical | |
| Operating temperature range | -20 to 65°C ( will typically operate well enough to even lower temperatures. See below for very cold operation) |
| Allowable temperature range | -40 to 65°C* See below for very cold operation |
| Storage temperature range | -40 to 85°C |
| Temperature Drift | 50 PPM/°C from -40 to 65°C ambient |
| Relative humidity | 0 to 90% non-condensing |
| Connections | Screw terminals accept 12 to 22 AWG wire |
| Terminal Tightening Torque | 0.5Nm [4.5in-lb] Screw terminal connectors |
| Overall Dimensions | 119 x 62 x 96 mm [4.68" x 2.45" x 3.79"] |
| Enclosure | 1/8 DIN, high impact plastic, UL 94V-0, color: gray (see drawing) |
| Mounting | 1/8 DIN panel cutout required. Two panel mounting bracket assemblies provided. |
| Weight | 162g [5.7oz] |
| Input | |
| Input Range | 4-20 mA |
| Input Overload | Over current protection to 2 A. |
| Accuracy | ±0.03% of span ±1 count, square root and programmable exponent: 10-100% FS. |
| Calibration | Calibrate or scale with or without signal source |
| Calibration Range | User programmable over entire display range of meter |
| Minimum Span | 0.40 mA between input 1 and input 2 Note: An Error message will appear if input is to low. |
| Function | Linear, square root, or programmable exponent |
| Low-Flow Cutoff | -99999 to 99999 (-99999 disables cutoff function) |
| Totalizer Features | |
| Totalizer | Calculates
total based on rate, time base of second, minute, hour, or
day, and field programmable multiplier; stored in non-volatile memory upon power loss. |
| Total Display | 0 to 99,999 main total display plus 0 to 999 total overflow for a combined 8 digit total of 99,999,999. |
| Alternating Display | Display may be programmed to alternate between rate and total every 10 seconds. |
| Time Base | Seconds, minutes, hours, or days |
| Totalizer Conversion Factor | 0.0001 to 99999 |
| Totalizer Rollover | Total rolls over when total exceed 99,999,999 |
| Totalizer Reset | Manual reset or automatic with time
delay, or disabled
for non-resettable total applications. |
| Open Collector Output Rating | Isolated open collector, 30 VDC @ 175 mA max. Can be used as an alarm output or pulse output |
| Pulse Output | 250 pulses/sec max; pulse width: 3
ms, fixed. If the pulse output
exceeds the maximum pulse output, counts are accumulated as pending and are not lost. One pulse per total increment, programmable from 0.0001 to 99999 (decimal point based on total selection). |
| Alarm | |
| Alarm Output | Assignable to total or high or low rate |
| Deadband (Hysteresis) | 0-100% of full scale, user selectable |
| Acknowledge | ACK button resets output and screen indication. |
| Automatic Reset | Alarm resets automatically when signal reaches the reset point. |
Pricing and mounting Dimensions
| Extreme cold operation | ||||
|---|---|---|---|---|
| Temperature | -30°C | -35°C | -37°C | -40°C |
| Contrast | Very Good | Good | Poor | Poor |
| Approximate Update Time | 9 sec | 15 sec | 25-28 sec | 40-46 sec |
| Note: For optimum cold temperature performance, set the “contrast” to max, increase the “filter” setting, and set “bypass” to minimum (advanced menu, see manual). | ||||