BO Detector Series Burned out heater elements cost time and money to diagnose. Don't let them cost you down time. Get the Burnout detector! Unique self-powered design saves complexity and wiring time.  The burnout detector works by sensing the AC current and activating at the specified set point. Sensing a repeatable specific trip-point, allows the burnout detector to monitor multiple parallel connected heater elements. The BO series can detect stalled motors by sensing the out of range current. In 3-phase operation (using a delta or 4-wire-Y configuration), of the Transtronics Burnout detector allows one sensor to monitor all three phases. Upon detection, it lights the LED and optionally activates an output.  Four basic output versions are available: LED lamp only, open collector, Triac and form C relay. Options include: large pass opening, adjustable set-point and remote mounting LED.


Applications:

Standard 0.875" Opening

Burn-out detector


Specifications

Set point current range (specify with order)

 to 1KA  (When setpoint is below 5A 5Vdc must be applied to pin 3)

Set point accuracy

+/-15% (5% on adjustable units) 10% dead-band

Output current Relay option

4A @ 220 Vac 5A@30Vdc/120Vac see drawing below for pin out

Triac output version

2A @ 220 Vac

Transistor output option

20 mA 24V (Pin 8 negative.; Pin 6 positive)

Ambient Operating Temperature

0 C to 60 C

Octal Case Size

2.75 X 1.75 X 2.375 inches (excluding octal pins)

Pass through opening

22.2mm [0.875"] Optional 31.7mm [1.25"] opening available

Adjustable versions available

 

Relay power supply

12V or consult factory

[] - denotes legacy units


Operation

3 phase
Burn out detector

Optional 1.25" Opening order -LD


Wiring Diagrams

wiring diagram

One or 3 Wire(s) with Ac current are threaded through opening.
No electrical contact is made with the current carrying wire

 

Remote mount LED wiring Pin 2 goes to + (plus) or the long lead
Pin 4 goes to - (minus) or the short lead. No dropping resister is required
Remote mount LED is not compatible with Triac version 

 

Din rail mountable bases are available as an accessory

 

Let Transtronics help you with your application. We want to help you solve your automation problems.



Ordering Information
Just call (785) 841 3089 - best to talk to our applications specialist first
Order number Price Description

BO-LED

$69.95 LED only

BO-OC

$79.95 Self powered Transistor output

BO-TRIAC

$89.95 With self powered 2A Triac output

BO-RELAY

$94.95 4 A Form C Relay output - requires external power

-RM

add $10.95 Remote mounted LED wiring option

-LD

add $29.95 Large pass through opening option 1.25" (31.7mm) 

-ADJ

add $39.95 Adjustable set point option

OCT-SOC


Din-rail/panel mountable octal base accessory
Visa MasterCard American Express
Minimum order $20.00
Domestic Payment Methods:
Personal checks
Money order
Bank checks
Visa MasterCard
Sorry No CODs

Prices subject to change.
Transtronics, Inc.3209 W.9th street
Lawrence, KS 66049
USA

Ph
FAX
Email
WEB

(785) 841 3089
(785) 841 0434
inform@xtronics.com
http://xtronics.com
Bookmark this page


Boolean: Case
Transtronics Home Page
See our line of industrial control electronics
  PLC's Index PC test equipment and EPROM programmer Process Control
Panel meters
Current sensors Resource library handbooks, primers and spec sheets

Corporate information and privacy statement
(C) Copyright 1994-2008, Transtronics, Inc. All rights reserved
Transtronics® is a registered trademark of Transtronics, Inc.