BO Detector Series Burned out heater elements cost time and money to diagnose. Don't let them cost you down time. Get the Burnout detector! Unique self-powered design saves complexity and wiring time. The burnout detector works by sensing the AC current and activating at the specified set point. Sensing a repeatable specific trip-point, allows the burnout detector to monitor multiple parallel connected heater elements. The BO series can detect stalled motors by sensing the out of range current. In 3-phase operation (using a delta or 4-wire-Y configuration), of the Transtronics Burnout detector allows one sensor to monitor all three phases. Upon detection, it lights the LED and optionally activates an output. Four basic output versions are available: LED lamp only, open collector, Triac and form C relay. Options include: large pass opening, adjustable set-point and remote mounting LED.
| Specifications | |
|---|---|
Set point current range (specify with order) |
to 1KA (When setpoint is below 5A 5Vdc must be applied to pin 3) |
Set point accuracy |
+/-15% (5% on adjustable units) 10% dead-band |
Output current Relay option |
4A @ 220 Vac 5A@30Vdc/120Vac see drawing below for pin out |
Triac output version |
2A @ 220 Vac |
Transistor output option |
20 mA 24V (Pin 8 negative.; Pin 6 positive) |
Ambient Operating Temperature |
0 C to 60 C |
Octal Case Size |
2.75 X 1.75 X 2.375 inches (excluding octal pins) |
Pass through opening |
22.2mm [0.875"] Optional 31.7mm [1.25"] opening available |
Adjustable versions available |
|
Relay power supply |
12V or consult factory |
[] - denotes legacy units

Optional 1.25" Opening order -LD

One
or 3 Wire(s) with Ac current are threaded through opening.
No electrical contact is made with the current carrying wire
Remote mount LED wiring Pin 2 goes to + (plus) or
the long lead
Pin 4 goes to - (minus) or the short lead. No dropping resister is
required
Remote mount LED is not compatible with Triac version
Din rail mountable bases are available as an accessory
Let Transtronics help you with your application. We want to help you solve your automation problems.
| Ordering Information Just call (785) 841 3089 - best to talk to our applications specialist first |
||
|---|---|---|
| Order number | Price | Description |
|
BO-LED |
$69.95 | LED only |
|
BO-OC |
$79.95 | Self powered Transistor output |
|
BO-TRIAC |
$89.95 | With self powered 2A Triac output |
|
BO-RELAY |
$94.95 | 4 A Form C Relay output - requires external power |
|
-RM |
add $10.95 | Remote mounted LED wiring option |
|
-LD |
add $29.95 | Large pass through opening option 1.25" (31.7mm) |
|
-ADJ |
add $39.95 | Adjustable set point option |
| Din-rail/panel mountable octal base accessory | ||
![]() |
Minimum order $20.00 Domestic Payment Methods: Personal checks Money order Bank checks Visa MasterCard Sorry No CODs |
|
Prices subject to change.
![]() | 3209
W.9th street Lawrence, KS 66049 USA |
Ph |
(785) 841 3089 (785) 841 0434 inform@xtronics.com http://xtronics.com |
Bookmark this page |
| Transtronics Home Page See our line of industrial control electronics |
PLC's Index | PC test equipment and EPROM programmer | Process Control Panel meters |
Current sensors | Resource library handbooks, primers and spec sheets |
Corporate information and
privacy statement
(C) Copyright 1994-2008, Transtronics, Inc. All rights
reserved
Transtronics® is a registered trademark of Transtronics, Inc.