- Heater
Burnout DetectorBO Detector Series Detect stalled motors or jammed conveyors with repeatability. The current detector works by sensing the AC current and activating at the specified set point. Sensing a repeatable specific trip-point, allows the detector to monitor multiple parallel loads. The BO series can detect stalled motors by sensing the out of range current. In 3-phase operation (using a delta or 4-wire-Y configuration), the Transtronics current detector allows one sensor to monitor all three phases for an unbalanced condition. Upon detection, it lights the LED and optionally activates an output. Four basic output versions are available: LED lamp only, open collector, Triac and form C relay. Options include: large pass opening, adjustable set-point and remote mounting LED.
| Specifications | |
|---|---|
| Set point current range (specify with order) | to 1KA (When setpoint is below 5A 5Vdc must be applied to pin 3) |
| Set point accuracy | +/-15% (5% on adjustable units) 10% dead-band |
| Output current Relay option | 4A @ 220 Vac |
| Triac output version | 2A @ 220 Vac |
| Transistor output option | 20 mA 24V (Pin 8 negative.; Pin 6 positive) |
| Ambient Operating Temperature | 0 C to 60 C |
| Octal Case Size | 2.75 X 1.75 X 2.375 inches (excluding octal pins) |
| Pass through opening | 22.2mm [0.875"] Optional 31.7mm [1.25"] opening available |
| Adjustable versions available | |
| Relay contacts | 5A@30Vdc/120Vac see drawing below for pin out |
| Relay power supply | 12V or consult factory |
[] - denotes legacy units

order option -LD

One or 3 Wire(s) with Ac current are threaded through opening.
No electrical contact is made with the current carrying wire
Remote mount LED wiring Pin 2 goes to + (plus) or the long lead
Pin 4 goes to - (minus) or the short lead. No dropping resister is required
Remote mount LED is not compatible with Triac version
Din rail mountable bases are available as an accessory
Let Transtronics help you with your application. We want to help you solve
your automation problems.
| Order number | Price | Description |
|---|---|---|
| BO-LED | $79.95 | LED only |
| BO-OC | $99.95 | Self powered Transistor output |
| BO-TRIAC | $109.95 | Self powered 2A Triac output |
| BO-RELAY | $119.95 | 4 A Form C Relay output - requires external power |
| -RM | add $15.95 | Remote mounted LED wiring option |
| -LD | add $34.95 | Large pass through opening option 1.25" (31.7mm) |
| -ADJ | add $34.95 | Adjustable set point option |
| -L24 | add $19.95 | External 24 power to LED (Pin 7) option |
| OCT-SOC | $5.97 | Din-rail/panel mountable octal base accessory Socket data sheet |
![]() |
Minimum order $20.00 Domestic Payment Methods: Personal checks Money order Bank checks Visa MasterCard Sorry No CODs |
Domestic shipping & standard handling $8.25 - up to 3 Lbs.
All shipping is by weight if more than 3 Lb. |
Prices subject to change.
![]() |
3209 W.9th street Lawrence, KS 66049 USA |
Ph |
(785) 841 3089 (785) 841 0434 inform@xtronics.com http://xtronics.com |
Bookmark this page |
| Transtronics Home Page See our line of industrial control electronics |
PLC's Index | PC test equipment and EPROM programmer | Process Control Panel meters |
Current sensors | Resource library handbooks, primers and spec sheets |
Corporate information and
privacy statement
(C) Copyright 1994-2006, Transtronics, Inc. All rights reserved
Transtronics® is a registered trademark of Transtronics, Inc.